Appendix F Environmental Data Electromagnetic Compatibility and Main Voltage Conditions
3BSE036351-510 A 435
Electromagnetic Compatibility and Main Voltage Conditions
Table 144. Electromagnetic Compatibility and Main Voltage Conditions
Environmental Specification
Compliance with
Standard
Environment Factor
Industrial
Environment
Electromagnetic Compatibility Conditions
Emission
–Radiated
–Conducted
Class A EN 55011
Immunity
–Radiated RF field
10V/m 80M - 1000MHz
3V/m 1.4G - 2.0GHz
1V/m 2.0G - 2.7GHz
EN 61000-4-3
Immunity
–Conducted RF field
10 V EN 61000-4-6
Immunity
–ESD (Electrical
Discharge)
±4kV contact discharge
±8kV air discharge
EN 61000-4-2
Immunity
–EFT/B (Electrical Fast
Transient/Burst)
±2kV power ports
±1kV other lines
EN 61000-4-4
Immunity
–Damped oscillatory
wave
IEC 60255-22-1
Immunity
–Power frequency
magnetic field
30 A/m, cont.
3 A/m for CRTs
EN 61000-4-8
Immunity
–Surge
±0.5kV common
±0.5kV differential
EN 61000-4-5